Hubbell HBL9450A requires conductors rated at 60° C?
- upvotes
- 5
- comments
- 7
Post
Highlighted: the lines this signal was extracted from
Looking at the installation manual for the HBL9450A it says: Select conductors having 90ºC or higher rated insulation having sufficient ampacity in accordance with the 60ºC column of National Electrical Code® Table 310-16 or Canadian Electrical Code Table 2. But then in the spec sheet it says: Operating Temperatures - Maximum continuous 75°C If the installation manual must be followed, then that means you'd need #6 conductors or better, regardless of whether it's Romex or THHN. If it's rated for 75°C then #8 conductors become a possibility.
Also quoted as evidence
[comment u/tuctrohs] Good catch. I've been saying the 75 C rating of the Hubbell / Bryant is one of the advantages vs. the Leviton EV rated, and this undermines that a bit.