Greetings! I have a site with several PCG1610 controllers, utilizing analog modulating valves for the heating and cooling. Recently, all of the valves were changed out with new Belimo valves and operators. The problem experienced, is the original valves were 0-10vdc, while the new valves are 2-10vdc. This is causing lag issues when calls for heating and cooling are placed. There is no option for 2-10vdc in the setup, and modifying the output for 19% minimum out does not help, it does not increase above 2vdc until the call exceeds 25%. Has anyone run into this before, and if so, what did you do to work around it? Thanks, appreciate any and all assistance!